Target U-value
Roof intentHow much insulation for roof?
Roof insulation often needs to balance thermal performance with structural depth. This page gives a simple roof-specific reference point.
Best for
- Flat roofs
- Pitched roofs
- Warm roof build-ups
Worked example
How much insulation is needed to reach 0.18 W/m²K?
The roof example below uses the same target-U method as the calculator: target resistance minus existing resistance, then multiply by lambda.
Example build-up
Target U-value 0.18 W/m²K, existing roof resistance 1.80 m2K/W, insulation lambda 0.035 W/mK.
Result
Required insulation thickness is approximately 9.9 cm.
Roof notes
Why roof thickness changes quickly
Structure depth
Roof build-ups often have tighter height limits than walls.
Thermal target
The lower the target U-value, the thicker the insulation usually becomes.
Check the deck
Existing resistance from the deck and finishes can change the result materially.