Amperage calculator: kW to amps for DC, single and three phase

Current depends on power, voltage and supply type. For 10 kW of active electrical input at PF = 1, 230 V single phase gives about 43.48 A; balanced three phase at 400 V gives about 14.43 A per line. Enter your own power and voltage below; do not add three line currents together.

Calculate with your assumptions

Change the example inputs as needed. Enter numbers without thousands separators; decimal points and commas are accepted. The supported scope and formula are described below.

Choose the correct supply and voltage

For DC, I = P / V. For single-phase AC active input, I = P / (V × PF). For balanced three phase, I = P / (√3 × U × PF), using line-to-line voltage U. Enter power in kW; the calculation multiplies it by 1000 to obtain watts. Power factor is ignored for DC.

Input power or shaft output?

When the equipment rating is mechanical shaft output, divide that power by efficiency η before calculating the electrical current. If the rating already states active electrical input, do not apply efficiency again. Apparent power in kVA is different from active power in kW; use the appropriate equipment rating. PF equals cos φ only for sinusoidal voltage and current.

Check the worked result

At 400 V balanced three phase, 10 kW shaft output with PF = 0.8 and η = 0.9 gives approximately 20.05 A per line. A 5 kW DC input at 230 V gives approximately 21.74 A. These examples state their assumptions and are not equipment or supply recommendations.

What current alone cannot determine

Cable cross-section, protective device rating, installation method, ambient temperature, grouping, voltage drop, fault protection and starting current need separate assessment. This steady-state calculator does not model harmonics, unbalanced phases, transient peaks or select a fuse, breaker or cable.

Examples with stated assumptions

Inputs and methodResult
10 kW input, 230 V, 1 phase, PF 143.48 A
10 kW input, 400 V, 3 phase, PF 114.43 A per line
10 kW shaft, 400 V, PF 0.8, η 0.920.05 A per line

Result scope

Schneider Electric's formula source was checked on 7 October 2026. Use the stated supply and power definition; current calculation is separate from installation design.