Avoid the factor-of-12 error between Btu·in/(h·ft²·°F) and Btu/(h·ft·°F). Compare both conductivity units with SI lambda and R per inch.

Author: Mindblown TechnologiesContent review:

Short answer

Btu·in/(h·ft²·°F) and Btu/(h·ft·°F) are different units of conductivity. One unit of the first is about 0.144228 W/(m·K); one unit of the second is about 1.730735 W/(m·K). Copying the same number between them changes the conductivity by a factor of 12.

On this page

Prepare your inputs

  • The complete conductivity unit, including the inch or foot convention.
  • The Btu definition and stated product/test conditions.
  • Thickness in a unit consistent with the selected calculation input.

Read the full unit beside k, not just the symbol

λSI ≈ 0.144227889 × kinch ≈ 1.730734667 × kfoot; kinch = 12 × kfoot

A US data sheet can express conductivity using an inch in the numerator or a foot in the denominator. Cancelling the dimensions does not make the numerical scales identical. Record the Btu basis as well: these examples use the international-table Btu conversion basis used by the linked material-layer calculator.

SI lambda is conductivity in W/(m·K). R per inch is a resistance per thickness, not conductivity. For the same homogeneous material and conditions, R per inch is the reciprocal of k only when k uses Btu·in/(h·ft²·°F).

Example: the same 0.25 means two different conductivities

With 0.25 Btu·in/(h·ft²·°F), lambda is about 0.036057 W/(m·K), and the corresponding US R per inch is 4. With 0.25 Btu/(h·ft·°F), lambda is about 0.432684 W/(m·K). That second conductivity is twelve times larger.

If the first value applies at the stated thickness and conditions, a 4-inch homogeneous layer has US R = 4/0.25 = 16. This illustrates arithmetic, not a promise that any product has constant R per inch across thicknesses, temperatures or densities.

Enter the unit that the existing calculator actually supports

The material-layer calculator accepts SI lambda, US k with an inch in the numerator, or US R per inch. Convert a foot-based k into the inch-based unit by multiplying its number by 12 before choosing the US k input. Check the unit displayed beside the field.

A unit conversion leaves the product, test conditions and declared-versus-design scope unchanged. It does not turn a material value into a complete assembly U-value.

Reference table

Equivalent conductivity numbers on the IT Btu basis; hypothetical values, not product declarations

k [Btu·in/(h·ft²·°F)]k [Btu/(h·ft·°F)]λ [W/(m·K)]US R per inch
0.10.0083330.01442310
0.20.0166670.0288465
0.250.0208330.0360574
0.30.0250.0432683.3333
0.40.0333330.0576912.5

Common mistakes

  • Entering foot-based k into an inch-based field without multiplying by twelve.
  • Treating R per inch as if it were a conductivity number.

Check before using the result

  • Match the displayed calculator unit to the converted value.
  • Record rounding and retain the original document value for traceability.
  • Keep conductivity conversion separate from selecting an assembly model.

Method limits

Values are rounded for display. Check the complete unit, Btu definition, product document and conditions before a calculation. No generic lambda or R per inch is assigned to an insulation material here.

Questions and answers

How do I enter foot-based k in the existing US k field?

Multiply the foot-based conductivity number by 12 to obtain Btu·in/(h·ft²·°F), then check that this is the unit displayed beside the input.

Does converting k into R per inch establish the R of a wall?

No. It changes the description of a homogeneous material under the same conditions. A wall calculation still needs its thicknesses, paths and boundary conditions.