Thermal insulation
Insulation thickness calculator
Calculate insulation thickness in mm and inches from your target RSI or US R-value and product lambda, k-value or R per inch.
Continue your calculation
How to use this calculator
Method and boundary
Choose target R units: SI m²·K/W or US h·ft²·°F/Btu. Enter material data as lambda, k or US R per inch. Changing units converts a positive value. Record the source of this layer's target R.
Thickness [m] = target layer R × design λ
Example
Target R = 3 m²·K/W with hypothetical λ = 0.040 gives 120 mm, about 4.724 in. US R = 13 with hypothetical R-4 per inch gives 3.25 in, or 82.55 mm.
This is nominal single-layer thickness. The calculator neither establishes target R nor selects stock thickness or assesses the complete assembly.
Calculation privacy
Recent activity remembers which calculator and page you used, the language, time and unit system in this browser. It does not save entered values or results.
How to calculate insulation thickness from R-value
For one homogeneous layer in SI, thickness in metres is d = R × λ. With target US R and k in Btu·in/(h·ft²·°F), thickness in inches is d = US R × k. With R per inch, use d [in] = target US R / R per inch. All data must describe the same material and conditions.
SI example: R = 3 and λ = 0.040
Target R = 3 m²·K/W with hypothetical λ = 0.040 W/(m·K) gives 3 × 0.040 = 0.12 m, or 120 mm. That is about 4.724 in. The result does not select an available stock size or establish the building's required R.
| Target US R | Thickness · in | Thickness · mm |
|---|---|---|
| R-13 | 3.25 | 82.55 |
| R-19 | 4.75 | 120.65 |
| R-30 | 7.5 | 190.5 |
Where does the target R come from?
From requirements applicable to the project and this layer's scope. Page language or location alone does not establish a target. A whole-assembly requirement is not necessarily the R of one extra insulation layer; first establish the missing resistance and other components.
Should I round the result to a board thickness?
Check available variants and their declared R at that thickness, then verify the requirement with the appropriate method. This tool gives nominal thickness; it does not approve combining boards, installation, moisture performance or whole-assembly properties.
Why not enter R-13 directly as SI R?
US R-13 is about 2.289 m²·K/W, not 13 m²·K/W. Choose the R unit in the form. Reusing the same number would overstate nominal thickness by about 5.678 times.
Check thermal product data · Calculate an existing layer's R
NIST SP 1038, §5.3.5–5.3.6 — k and U unit conversion source on the IT Btu basis; examples are our own calculations.