Target U-value
Ground floor intentHow much insulation for ground floor?
Ground floors often have some resistance from the slab and perimeter details, but the target U-value still drives the insulation thickness.
Best for
- Ground floors
- Slab-on-grade floors
- Perimeter-insulated floors
Worked example
How much insulation is needed to reach 0.20 W/m²K?
Ground floor calculations should include the resistance already provided by the slab and any underfloor layers.
Example build-up
Target U-value 0.20 W/m²K, existing floor resistance 1.10 m2K/W, insulation lambda 0.035 W/mK.
Result
Required insulation thickness is approximately 11.6 cm.
Floor notes
Why ground floors differ
Slab on grade
Ground contact changes the effective thermal path compared with a suspended floor.
Perimeter losses
Edges and junctions can matter a lot on ground-contact floors.
Build-up height
Underfloor insulation has to fit the overall floor depth available in the project.