US R-value tools

R-value to U-factor calculator

Use this converter when a US insulation label, wall schedule, or code table gives R-13, R-19, R-30, R-49, or another R-value and you need the equivalent U-factor. In US units the relationship is direct: U-factor equals one divided by R-value. The page also shows SI U-value because international reports often ask for W/m²K. That SI number is not the same as the simple inverse of the US R-value; the US U-factor must be multiplied by 5.678263337.

Calculations keep US R-value, U-factor, SI R, and SI U-value separate so an inverted value is not mislabeled.

Quick answer

R-value to U-factor calculator

Formula: U-factor = 1 / R-value. R-13 gives 0.077, R-19 gives 0.053, R-30 gives 0.033, and R-49 gives 0.020 Btu/(h·ft²·°F). These are rounded planning values for the same unit system.

Formula
U_factor = 1 / R_US
Example
Example: R-19 converts to U-factor 0.053 and SI U-value 0.299 W/m²K.

Working calculator

Enter the core dimensions and check the result directly on this page.

U-factor0Btu/(h·ft²·°F)
U-value0W/m²K

R-value conversion table

Common R-values shown with US U-factor and metric SI U-value.

InputUS U-factorSI U-valuePractical reading
R-130.0770.437 W/m²Kcommon cavity insulation
R-190.0530.299 W/m²Ktypical wall check
R-300.0330.189 W/m²Kstronger layer
R-490.0200.116 W/m²Khigh resistance

Worked examples

Example 1

Inputs

  • R_US = 13

Formula

U_factor = 1 / R_US

Steps

  1. 1 / 13 = 0.0769

Result

U-factor = 0.077 Btu/(h·ft²·°F)

Related calculator

R-value to U-factor

Example 2

Inputs

  • R_US = 49

Formula

U_factor = 1 / R_US

Steps

  1. 1 / 49 = 0.0204

Result

U-factor = 0.020 Btu/(h·ft²·°F)

Related calculator

R-value to U-factor

R-value to U-factor calculator

Example: R-19 converts to U-factor 0.053 and SI U-value 0.299 W/m²K.

Zero and negative values are not meaningful for these conversions. The calculator clamps inputs above zero and the text explains which unit system each value belongs to.

Practical note

How to interpret the calculator result

R-value to U-factor calculator is intended for quick option checks and technical discussion before detailed execution. The result depends on the selected units, declared material values, and chosen surface resistances, so each change in layer or thickness should be treated as a separate variant.

The calculator does not automatically verify every local rule, thermal bridge, moisture condition, structural connection, or installation tolerance. If the result is close to a requirement, treat it as a reason for deeper verification rather than a final decision.

For better comparisons, test several realistic thicknesses, check current product data sheets, and review the complete assembly. A calculated value is most useful when the assumptions are clear: material, thickness, layer order, units, and data source.

For insulation or U-value tools, layer order and correct units are especially important. For concrete, electrical, plumbing, or heating tools, the result should be read as a quick quantity or plausibility check before standards and execution conditions are reviewed.

Save the result with the date, material name, and assumptions. If the product, diameter, cable section, or thickness changes later, do not compare the numbers alone without checking which inputs changed.

For calculator pages, clear separation between inputs and result is essential. If a value looks surprising, check units and default fields first, then review the project assumptions.

R-value to U-factor Calculator

R-value to U-factor Calculator

Convert a US insulation R-value to U-factor with U-factor = 1 / R-value, plus SI U-value for comparison.

Assembly thickness

Assembly thickness

Use thickness in inches with k-value, or switch to metric mode for millimetres and lambda. The calculator labels each unit before showing the result.

U-value

U-value

R-value and U-factor move in opposite directions: higher R-value is better, while lower U-factor or lower U-value is better.

CategoryLambdaLayerMaterialThickness

How it works

Unit assumptions

The input is a US R-value in h·ft²·°F/Btu. If you start from RSI in m²K/W, convert RSI to US R-value first by multiplying by 5.678263337.

How to use the result

For assemblies, convert the total effective R-value, not only the labeled cavity insulation. Framing, edge losses, and air leakage can raise the final U-factor.

R-value to U-factor Calculator

Formula: U-factor = 1 / R-value. R-13 gives 0.077, R-19 gives 0.053, R-30 gives 0.033, and R-49 gives 0.020 Btu/(h·ft²·°F). These are rounded planning values for the same unit system.

Use U-factor when comparing windows, doors, skylights, and whole assemblies that are reported as heat transfer. Use R-value when comparing insulation layers or products that add resistance. The converter rejects zero and negative values because a material cannot have zero positive resistance in this relationship.

Add layerRestore default setupRemove
Assembly nameThickness unitInternal Rsi (m2K/W)External Rse (m2K/W)

Calculation assumptions

The calculators use visible formulas and explicit unit conversions. Treat the result as a preliminary check, not a complete building design.

Review: 2026-04-27
  • SI and US units are converted separately; R, RSI, U-value, and U-factor are not mixed without the unit factor.
  • Enter positive values and compare the result with the selected product datasheet.
  • Local codes, thermal bridges, fasteners, and installation quality can change the requirement.
  • Last formula review: 2026-04-27.

Next useful step

US R-value mini-hub

Move between R-value calculators, material tables, insulation comparisons, and assembly calculators without scanning the whole navigation.

Next step

Open the closest calculator, reference, or methodology page instead of scanning a long list.

Lambda table

Check conductivity before entering material assumptions into a calculator.

Open

R per inch

Use this when working with US-style R-value specifications.

Open

R-value conversion FAQ

No. Zero resistance or zero transmittance would make the inverse formula impossible or physically meaningless.

They describe heat transfer in different unit systems. US U-factor uses Btu/(h·ft²·°F), while SI U-value uses W/m²K.

Higher is better for R-value because it is resistance. Lower is better for U-factor and U-value because they measure heat transfer.

Use them for checks and comparisons, then confirm manufacturer declarations, assembly corrections, and local code rules.

Yes. It is designed for layered assemblies such as external walls, flat roofs, pitched roofs, floors, and slabs. For unusual assemblies, add every relevant layer and treat the result as a planning check before formal verification.

Yes. It is intended for fast concept-stage calculations, insulation comparison, and envelope optimisation before detailed design. It is best used to narrow choices, not to replace a code check or project-specific thermal bridge assessment.

Yes. You can switch between millimeters, centimeters, and inches, and the calculator keeps the values consistent. For fewer mistakes, choose one unit system at the start of a project and review converted thicknesses before export.

Use R-value to U-factor calculator as a first-pass reference. Before specifying anything, compare the result with the temperature range, actual project dimensions, product data sheet, and local requirements.